Generator Service & Maintenance Programs

READING ELECTRIC'S GENERATOR SERVICE PROGRAM COMPARISON
BRONZE program SILVER Program GOLD program
Cooling System: X X X
Check for proper block heater operation X X X
Check coolant level (Includes adding up to 2 gallon to fill to proper level) X X X
Check coolant for proper freeze protection X X X
Check coolant for proper PH (Includes adding up to 1 pint of conditioner as needed) X X X
Replace coolant filter annually X X X
Visual inspection of radiator for leaks X X X
Inspect radiator cap for cracks and leaks X X X
Check coolant hose condition X X X
Check engine belts X X X
Inspect water pump for signs of leakage X X X
Starting Battery System: X X X
Check and record battery charger float voltage X X X
Record battery installation date X X X
Visual inspection of battery condition X X X
Check and tighten cable connections as needed X X X
Check electrolyte level in battery X X X
Check and record minimum dip voltage while cranking X X X
Test and record battery cold cranking amp output X X X
Check charger output current X X X
Fuel System: X X X
Test day tank pump for proper operation X X X
Check condition of flexible fuel lines X X X
Check fuel injection pump for leaks X X X
Check vents on gas regulator for obstruction X X X
Engine Ignition System: X X X
Check distributor cap & rotor for signs of damage X X X
Check ignition points for excessive wear X X X
Check high voltage ignition wires for cracks or damage X X X
Engine: X X X
Check engine oil level X X X
Check engine oil appearance X X X
Drain and replace engine oil annually X X X
Replace engine lube oil filters X X X
Visual inspection for oil leaks X X X
Inspect air filters for dirt and deterioration X X X
Replace fuel filter annually or every 100 hours X X X
Visual inspection of engine and generator mounts X X X
Ensure proper operation of starter motor X X X
Check governor oil level and add oil as needed X X X
Check governor linkage X X X
Check governor belt condition and tension X X X
Check for proper governor response & stability X X X
Operational Checks: X X X
Visual inspection of meter & gauge readings X X X
Check and record generator output voltage X X X
Check and record AC current X X X
Check and record frequency of generator X X X
Check and record hours since last service X X X
Check and record alternator output voltage X X X
Check and record engine oil pressure X X X
Check and record engine water temperature X X X
Test pre-alarms for proper operation X X X
Test engine safety shutdowns if accessible X X X
Check intake and exhaust louver operation X X X
Exhaust System: X X X
Visually inspect exhaust system for leaks X X X
Check exhaust drain valve for blockage X X X
Inspect exhaust flex pipe for cracks and damage X X X
Check rain cap for proper opening/closing X X X
No Load Test of the Generator only: X X X
Transfer Switch: X X
Annual Transfer of Power Test X X
Torque Power Lugs X X
Clean Contacts X X
Verify current firmware, update if nessecary X X
Clean the enclosure X X
Infrared Thermography verfication X X
Bi-Annual Inspection: X X
Animal Deterence X X
Battery Test X X
Check Oil Level X X
Check & Clear Faults X X
Verify Hours since last service X X
Infrared Thermography verfication (when the Transfer Switch is outside) X X
Visual inspection of radiator for leaks X X
Generator Monitoring System: X
Availability of Site Power X
Availability of Utility Power X
Generator Status – Running or Not Running X
Generator Fault Status X
Battery Level (meaning the “true” battery level not including input from the battery charger X
Load Test: X
Annual Transfer to Generator Power X
Load Testing every three years when you sign up for 3 min. three year contract X
Support to reset Clocks and other electronics X
MORE, MORE, MORE X
Service Performance Priority for Emergergency Repairs: X
Warranty Record Tracking: X

Services and Materials NOT included:

  • Non-Consumable Repair Parts
  • Emergency or after hour calls
  • Load Testing